Modbus protocol

Modbus is a data communications protocol originally published by Modicon in 1979 for use with its programmable logic controllers. Modbus has become a de facto standard communication protocol and is now a commonly available means of connecting industrial electronic devices.

Available solutions




This template is for Zabbix version: 7.0
Also available for: 6.4 6.2 6.0 5.4

Source: https://git.zabbix.com/projects/ZBX/repos/zabbix/browse/src/go/plugins/modbus?at=release/7.0

Modbus plugin

This plugin provides a native solution for monitoring modbus devices by Zabbix. The plugin can monitor several modbus devices simultaneously via Zabbix agent 2. Both TCP and RTU connections are supported.

Requirements

  • Zabbix Agent 2
  • Go >= 1.12 (required only to build from source)

Installation

The plugin is supplied as part of the Zabbix Agent 2 and does not require any special installation steps. Once Zabbix Agent 2 is installed, the plugin is ready to work. Now you need to make sure that a modbus device is available for connection and configure monitoring.

Configuration

Open the Zabbix Agent configuration file (zabbix_agent2.conf) and set the required parameters.

Plugins.Modbus.Timeout — request execution timeout (how long to wait for a request to complete before shutting it down).
Default value: equals the global 'Timeout' (configuration parameter set in zabbix_agent2.conf).
Limits: 1-30

Named sessions

Named sessions allow you to define specific parameters for each instance of modbus device. Currently, only three parameters are supported: Endpoint, SlaveID and Timeout (if certain parameter is not specified for a named session, a value from key will be used).

Example:
If you have two instances: "MB1" and "MB2", the following options have to be added to the agent configuration:

Plugins.Modbus.Sessions.MB1.Endpoint=tcp://127.0.0.1:502
Plugins.Modbus.Sessions.MB1.SlaveID=20
Plugins.Modbus.Sessions.MB1.Timeout=2
Plugins.Modbus.Sessions.MB2.Endpoint=rtu://com1:9600:8n1
Plugins.Modbus.Sessions.MB2.SlaveID=40
Plugins.Modbus.Sessions.MB2.Timeout=4

Now, these names can be used as connStrings in keys instead of URIs:

modbus.get[MB1]
modbus.get[MB2,,,30001,1,uint64,le,0]

Parameters priority

Zabbix checks parameters in the following order:

  1. Item key parameters (checked first).
  2. Named session parameters in configuration file (Plugins.Modbus.Sessions.<sessionName>.<parameter>). Checked only if values provided in a key parameters are empty. →

Supported keys

modbus.get[endpoint,slaveid,function,address,count,type,endianness,offset] — receive value from modbus device Params:

  • endpoint — tcp or rtu connection string. tcp://localhost:511 rtu://COM1:9600:8n1
  • slaveid — Modbus address of the device. Optional.
  • function — 1,2,3,4 modbus read functions. Optional.
  • address — Address of first registry , coil or input. Default 00001. Optional.
  • count — count of number for return. Default 1. Optional.
  • type — acceptable values: bit, int8, uint8, uint16, int16, uint32, int32, float, uint64 and double. Default bit or uint8. Optional.
  • endianness — acceptable values: be, le, mbe, mle. Optional.
  • offset — Number of registers or bits, starting from 'address', the result of which will be discarded. Optional. Returns: Array of numbers in JSON format.

Troubleshooting

The plugin uses Zabbix Agent logs. To receive more detailed information about logged events, consider increasing a debug level of Zabbix Agent.

Não encontrou a integração que vocá precisa?